| Specification | |
| AC input system | 220/380 V AC three-phase four-wire |
| AC power distribution | AC input: one 4-pole 63 A circuit breaker, one 4-pole 63 A circuit breaker (backup, manual switch, mechanical interlock)
AC output: three 1-pole 16 A circuit breakers |
| DC power distribution | Three users in total, each of which includes:
LLVD: two 1-pole 125 A circuit breakers; one 1-pole 125 A circuit breaker can be added. BLVD: two 1-pole 63 A circuit breakers Common load circuit breaker: one 1-pole 32 A circuit breaker Battery: four 1-pole 125 A circuit breakers; one 1-pole 125 A circuit breaker can be added. |
| AC surge protection | Nominal surge discharge current: 30 kA (8/20 µs), fiv times respectively in the positive and negative directions |
| Operating temperature | –40°C to +65°C; when the operating
temperature ranges from 55°C to 65°C, rectifier power is derated automatically |
| Operating humidity | 5%–90% RH (non-condensing) |