ETP48600-C5A8 Introduction
ETP48600-C5A8 with 8*75A rectifier, fully loaded, 1*SMU06T
The ETP48600 embedded power system is a distributed power supply and power backup solution which is developed based on the Open Computer Project (OCP) 2.0 standard and designed for data centers. This solution features high efficiency, energy saving, high capacity, modular deployment, quick discharge at a high rate, flexible power backup, high reliability, environmental friendliness, and easy maintenance. It applies to large data center scenarios with +48 V servers.
The ETP48600 embedded power system consists of two subsystems, namely, TIEN1 power system and ESS4815A lithium battery system.
The TIEN1 power system supports 240 V/415 V AC power input, and supplies +48 V DC power to equipment in a data center after converting AC power into DC power.
The ESS4815A lithium battery system serves as the power backup unit of the ETP48600. A single lithium battery system supports 7.5 kW power output. A maximum of four ESS4815A lithium battery systems can be cascaded.
Site monitoring unit: SMU06T
ETP48600-C5A8 Datasheet
| Specification |
| AC input system |
220/380V AC Three-phase, four-wire |
| AC Input |
100A/4P×2, manual switching, mechanical interlock |
| Output current |
MAX 600A |
| Protection level |
IP20 |
| DC distribution |
User 1: LLVD: 100A/1P×3,63A/1P×2 BLVD: 32A/1P×2 User 2: LLVD: 32A/1P×4 BLVD:16A/1P×2 Battery circuit breaker: 125A/1Px 4, support expansion to add 125A/1Px2 circuit breaker |
| AC output |
16A/1P×3 |
| Operating temperature |
–40°C to +65°C; when the operating
temperature ranges from 55°C to 65°C,
rectifier power is derated automatically
|
| Operating humidity |
5%–90% RH (non-condensing) |