Huawei S16700 Series Switches CR8MP2KHDCC0 380VDC HVDC and 220V AC Power Distribution Unit.
Mappings between CR8MP2KHDCC0 and product models
Product
Product Model
First Supported Version
S16700-4
EX1BS16704SA0 (02355HUL)
V600R022C10
S16700-4
EX1BS16704SA0 (02355HUL-001)
V600R024C10
S16700-8
EX1BS16708SA0 (02355HUN)
V600R022C10
S16700-8
EX1BS16708SA0 (02355HUN-001)
V600R024C10
Functions and Features
A 380 V high-voltage DC PDU supports 240 V/380 V DC and 220 V AC power input and provides two output groups A1 and B1. Each group controls four HVDC-3Z-03 sockets. When the groups are connected to a chassis, the total current of all sockets in each group cannot exceed 63 A.
Technical specifications of the CR8MP2KHDCC0
Item
Specification
Dimensions without packaging (H x W x D) [mm(in.)]
With mounting brackets: 43.6 mm x 484 mm x 60 mm (1.72 in. x 19.06 in. x 2.36 in.) (excluding the raised terminal)
Without mounting brackets: 43.6 mm x 442 mm x 60 mm (1.72 in. x 17.40 in. x 2.36 in.) (excluding the raised terminal)
Weight without packaging [kg(lb)]
2.1 kg (4.63 lb)
Rated input voltage [V]
HVDC: 240 V/380 V
AC: 220 V
Rated output voltage [V]
HVDC: 240 V/380 V
AC: 220 V
Maximum input current [A]
63 A
Maximum output current [A]
16 A
Number of inputs
two three-row terminal blocks
Number of outputs
Eight HVDC-3Z-03 sockets for power output
Front-end circuit breaker/fuse [A]
63 A
CR8MP2KHDCC0 FAQ
Q1: Which Huawei switch models are specifically compatible? Does it support automatic dual-input switching?
A1: Compatible with Huawei S7700 (S7703/S7706/S7712), S9700 (S9703/S9706/S9712), and S12700 (S12704/S12708/S12710/S12712) series; supports automatic dual-input switching with seamless fault switching.
Q2: How is intelligent monitoring implemented? Is additional software configuration required?
A2: Supports SNMP protocol access to the data center monitoring system, or status viewing through the Huawei iMaster NCE management platform; no additional monitoring software purchase is required, basic monitoring functions are supported by default.
Q3: How many of these PDUs are needed per switch? A3: It is recommended to equip each core switch with 1-2 units. One unit can meet the basic redundancy power supply, and two units can achieve dual backup (adapted to ultra-core scenarios). The specific configuration depends on the power requirements of the switches and the redundancy standards of the data center.